  Datasheet File OCR Text:
 FCP600-48 AC-DC Front End Data Sheet 48V Output, 600 Watts
Advance Product Release
Features * RoHS lead-free solder and lead-solder-exempted products are available * Wide input voltage range 85-264 VAC * Two outputs (one high current output) * Low conducted and radiated EMI (EN 55022 class B) * UL recognized to UL 60950/CSA 22.2 No. 60950-00, and TUV approved to EN 60950-1 * High density design 4" x 1.65" x 8.5" cassette * Highly-efficient topology * 100 kHz I2C interface * Overtemperature, output overvoltage, and output overcurrent protection * Supervisory signaling * Included ORing diode for true redundant operation
Applications * Telecommunications equipment
Description The FCP600-48 is a highly-efficient ac-dc power supply with one high current output and an auxiliary standby output, which can be used in a wide range of applications. Passive current share along with internal ORing diodes allow this unit to be also used in redundant, hot-swap applications. The FCP600-48 meets international safety standards and displays the CE Mark for the low Voltage Directive.
Model Selection
Model Input Voltage VAC 85-264 Output 1 Vo nom VDC 48 Io max ADC 13 Standby Output Vo nom Io max VDC ADC 3.35 2.5 Rated Power W 632
FCP600-48
Ordering Information
Options RoHS lead solder exemption RoHS compliant for all 6 substances Suffixes to Add to Part Number No RoHS suffix character required. Add "G" as the last character of the part number.
OCT 30, 2006 revised to NOV 10, 2006
Page 1 of 6
www.power-one.com
FCP600-48 AC-DC Front End Data Sheet 48V Output, 600 Watts
Absolute Maximum Ratings Stresses in excess of the absolute maximum ratings may cause performance degradation, adversely effect longterm reliability, and cause permanent damage to the converter.
Parameter Input Voltage Operating Temperature Storage Temperature Conditions/Description Continuous Transient, 60 ms Ambient Vi min-Vi max, Io nom, cooling by internal fan Non-operational Min Max 264 300 55 85 Units VAC VAC C C
0 -40
Environmental, Mechanical, & Reliability Specifications All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter Operating Humidity Storage Humidity Shock Sinusoidal Vibration Conditions/Description Relative humidity, non-condensing Relative humidity, non-condensing IEC/EN 60068-2-27, 11 ms IEC/EN 60068-2-6 2-8 Hz 8-200 Hz 200-500 Hz MIL-HDBK-217F Notice 2, GB, 25 C Min 10 5 Nom Max 90 95 30 Units % % gn mil gn gn kh
7.5 2 4 TBD
MTBF
Isolation Specifications The electric strength test is performed in the factory as routine test in accordance with EN 550116, IEC/EN 60950, and UL 1950 and should not be repeated in the field. Power-One will not honor any warranty claims resulting from electric strength field tests.
Parameter Insulation Safety Rating Conditions/Description Input/Case Input/Output Output/Case Input/Case Input/Output Output/Case Min Nom Max Basic Reinforced Functional Units
Electric Strength Test Voltage
2.121 3.6 0.5
kVDC kVDC kVDC
OCT 30, 2006 revised to NOV 10, 2006
Page 2 of 6
www.power-one.com
FCP600-48 AC-DC Front End Data Sheet 48V Output, 600 Watts
EMC Specifications All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter Electrostatic Discharge Electromagnetic Field Electr. Fast Transients / Burst Surge Voltage Dips and Interruptions RF Conducted Immunity Emissions Radiated/Conducted Harmonics Voltage Fluctuation and Flicker Description IEC/EN 61000-4-2, level 4 (contact/air) IEC/EN 61000-4-3, level 3 IEC/EN 61000-4-4, level 3 (direct/capacitive) IEC/EN 61000-4-5, level 3 (L/L, L/C) IEC/EN 61000-4-11 IEC/EN 61000-4-6 CISPR 22/EN 55022/EN 61204 IEC/EN 61000-3-2 IEC/EN 61000-3-3 Criterion 8/15 kV, criterion B 10 V/m, criterion A 2/1 kV, criterion B 1/2 kV, criterion B Criterion B 10 VAC, AM 80%, 1 kHz, criterion A Class B Class B Pass
Input Specifications All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter Input Voltage Turn-On Input Voltage Turn-Off Input Voltage Input Frequency Inrush Current Limitation Power Factor Efficiency Conditions/Description Ramping up Ramping down 115/230 VAC Vi nom, Io nom Vi = 230 VAC, Io nom Min 85 70 70 47 0.96 88 Nom 115/230 50/60 Max 264 85 85 63 20 Units VAC VAC VAC Hz A %
Output Specifications All specifications apply over specified input voltage, output load and temperature range unless otherwise noted.
Parameter Output Voltage Setpoint Accuracy Output Current V1 Standby Output Static Line Regulation V1 Static Load Regulation V1 (Droop Characteristic) Hold-Up Time Dynamic Load Regulation Conditions/Description Vi = 230 VAC, Io1 @ 6.5 ADC, TC = 25 C Min -0.5 0 0 -0.5 -250 20 -2 2 400 1 120 Nom 13 2.5 Max 0.5. 14.3 2.75 0.5 Units % Vo nom ADC ADC % Vo nom mV/A ms % Vo nom s s mVpp
Vi min-Vi max, Vi nom, 0-100% Io nom Vi min-Vi max, Vi nom, 0-100% Io nom Starting at Vi = 230 VAC, Po nom Load change = 33%, dIo/dt = 2A/s voltage deviation recovery time Vi nom, Io nom Vi nom, Io nom, 20 MHz bandwidth
Start-Up Time Output Voltage Ripple and Noise
OCT 30, 2006 revised to NOV 10, 2006
Page 3 of 6
www.power-one.com
FCP600-48 AC-DC Front End Data Sheet 48V Output, 600 Watts
Protection All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter Input Fuse Input Transient Protection Output Conditions/Description Not user accessible With varistor No-load and short circuit proof short circuit proof overload (latch style) Latch style Automatic power shutdown at TC = TBD Min Nom Max 12.5 AT Units
Overvoltage Protection Overtemperature Protection
110 110
130 115
% Io nom % Io nom % Io nom % Vo nom
Control All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter I2C Digital Bus PS Seated Signal PS Remote Shutdown AC fail pre-warning (I2C & OC)* DC fail (I2C & OC)* Temperature Warning (I2C & OC)* Fan OK (I2C & OC)* Current Share Status Indication Conditions/Description Reports information and monitors alarm functions Contact closure to GND TTL compatible signal, inhibited at High or TTL "1" Supervisory AC input voltage; Pre-warning time >6 ms Supervisory under- and overvoltage pre-ORing diode of V1 Indicates if unit is operating normally or in overtemperature, Pre-warning time >10 ms Indicates if fan is operating or has failed Droop load characteristic for V1 LEDs: DC OK (green), AC OK (green)
* Signal providing by I2C interface (I2C) or by open collector (OC) Features All specifications apply over specified input voltage, output load and temperature range, unless otherwise noted.
Parameter Fan speed control C supply voltage in-/output (Pin 10) Conditions/Description 2 fan speed levels depending on internal heat sink temperature 2 Fan speed level and temperature information available on I C digital bus If unit is operating: 5 to 7V is provided at pin 10. If unit is NOT operating, pin 10 is input from a parallel connected unit for C supply.
OCT 30, 2006 revised to NOV 10, 2006
Page 4 of 6
www.power-one.com
FCP600-48 AC-DC Front End Data Sheet 48V Output, 600 Watts
Characteristic Curves:
91 90 89 88 Eta [%] 87 86 85 84 83 82 86 122 158 194 230 266 -5
55 Temp [C]
Vi [V]
Figure 1. Efficiency vs. Input Voltage and Ambient Temperature, Io = Io nom
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
OCT 30, 2006 revised to NOV 10, 2006
Page 5 of 6
www.power-one.com
FCP600-48 AC-DC Front End Data Sheet 48V Output, 600 Watts
Mechanical Data
Mechanical Data (H, W, D) 4" (101.6mm) x 1.65" (41.9mm) x 8.5" (215.9mm)
Output Connector Descriptions
Rear View
Connector: Molex (15-06-0241)
Output Connector
Description 48V Output 48V Output RTN AC-fail, DC-fail, Temp.fail Power Supply Present Signal Serial Data Line Serial Clock Line Address Input Line A0 5 to 7V FAN FAIL PS Enable 3.35V Standby RTN 3.35V Standby OCT 30, 2006 revised to NOV 10, 2006
Pin Location 4,5,6,16,17,18 1,2,3,13,14,15 9 23 11 12 21 10 24 22 7 19 Page 6 of 6
Reference Name Vo1 Vo1 RTN PF PSPRES SDA SCL A0 C supply voltage bus FF PSEN Vo2 RTN / Logic Ground / 5 to 7V RTN Vo2 www.power-one.com


▲Up To Search▲   

 
Price & Availability of FCP600-48

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X